Sixteen-channel discrete output modules – Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual

Page 50

Advertising
background image

Publication 1734-UM016A-EN-P - October 2010

44 1734/1738 I/O Module Assembly Information

This POINT I/O input module produces 2 or 3 bytes of input data based on
which produced assembly is selected. The default assembly instance 101 is 3
bytes. This module does not consume I/O data.

Sixteen-channel Discrete Output Modules

Use the table shown below for the following modules:

• 1738-OB16E19M23
• 1738-OB16E25DS
• 1738-OB16EM12

Configuration Assembly Instance 103

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Input Off to On Filter Low Byte

1

Input Off to On Filter High Byte

2

Input On to Off Filter Low Byte

3

Input On to Off Filter High Byte

4

Produced Assembly

5

Reserved = 0

Produced Diagnostic Input Data Assembly Instance 101

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ch 7

Ch 6

Ch 5

Ch 4

Ch 3

Ch 2

Ch 1

Ch 0

1

Ch 15

Ch 14

Ch 13

Ch 12

Ch 11

Ch 10

Ch 9

Ch 8

2

Reserved

Fault LED
State

SSV Fault
12…15

SSV Fault
8…11

SSV Fault
4…7

SSV Fault
0…3

Produced Input Data Assembly Instance 5

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ch 7

Ch 6

Ch 5

Ch 4

Ch 3

Ch 2

Ch 1

Ch 0

1

Ch 15

Ch 14

Ch 13

Ch 12

Ch 11

Ch 10

Ch 9

Ch 8

Configuration Assembly Instance 123

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Enable
Latched Faults

Idle Value

Idle Action

Fault Value

Fault Action

1

Reserved = 0

Advertising