Rockwell Automation 1738 Assembly Connections for POINT I/O and ArmorPOINT I/O EtherNet/IP Adapters User Manual
Page 25
Publication 1734-UM016A-EN-P - October 2010
Using an Assembly Connection 19
Controller Tags by right-clicking the Controller Tags option from the
Controller Organizer pane. Select Monitor Tags.
Monitor Tags
You should see three Tags with the module's name. They will have an C, I, or
O suffix denoting Configuration, Input, or Output respectively. Note that the I
and O Tags are sized according to the sizes that were entered on the properties
page. The C Tag always has 400 bytes allocated for it regardless of the size
specified.
Add Configuration Header
Bytes 0…9 must contain the minimum configuration header information
described in Minimal Adapter Configuration Assembly. As can be seen from
the figure below, the Chassis Size is set to 0x12 (18 decimal). The produced