Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014

19

Install Your Module Chapter 4

2.

Drill the necessary holes for #6 (M3) pan head screws.

3.

Mount the module using #6 (M3) screws.

Mount the Module in High Vibration Areas

If you mount the module in an area that is subject to shock or vibration, we
recommend you use a flat and a lock washer to mount the module. Mount the flat
and the lock washer as shown in the mounting illustration. Torque the mounting
screws to 0.68 Nm (6 lb-in.).

High Vibration Area Mounting

Wire the Module

The 1732E-OB8M8SR and 1732E-IB8M8SOER ArmorBlock EtherNet/IP
modules have 3-pin pico-style I/O connectors. We provide caps to cover the
unused connectors on your module. Connect the quick-disconnect cord sets you
selected for your module to the appropriate ports.

I/O Connectors

Refer to the pinout diagrams for the I/O connectors.

Pico-style 3-Pin Input Female Connector

45768

Lock washer

Flat washer

(View into connector)
Pin 1 Sensor source voltage
Pin 3 Return
Pin 4 Input