Configurable point-level output fault states, E configurable point-level output fault states – Rockwell Automation 1732E-OB8M8SR EtherNet/IP Dual Port 8-Point SOE Input and Scheduled Output Modules UM User Manual

Page 71

Advertising
background image

Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014

61

Specific Features of the 1732E-OB8M8SR Scheduled Output Module Chapter 9

Configurable Point-Level
Output Fault States

Individual outputs can be independently configured to unique fault states, either
On, Off, or Hold in case of a communication failure or Program mode.

Through the RSLogix 5000 software, the user can set output state during
Program Mode and Fault Mode for channels 0…7. Valid values are On, Off, and
Hold.

Fault Duration can be set with 1, 2, 5, 10 seconds and Forever or 0.

Fault Final State can be set as On or Off. On the Configuration tab, it is grayed
out unless Fault Duration is something other than "Forever".

Follow these steps to enable a fault state.

1.

On the Module Properties dialog box, click the Configuration tab.

2.

Click the pull-down arrow to choose the Program Mode for each channel.
Options available are Off (default), On and Hold.

3.

Click the pull-down arrow to choose the Fault Mode for each channel.
Options available are Off (default), On and Hold.

IMPORTANT

Whenever you inhibit an output module, it enters the
Program mode and all outputs change to the state
configured for the Program mode. For example, if an
output module is configured so that the state of the outputs
turn off during Program mode, whenever that module is
inhibited, the outputs will turn off.