2-8 Installing the PROFIBUS Adapter

Wiring Connections

Proceed as follows. Make all connections to the removable terminal
block (RTB).

1. Connect chassis ground to terminal 2.

2. Connect 12/24V supply positive lead to terminal 6.

3. Connect 12/24V negative lead to terminal 4.

External power applied across terminal 6 (+) and 5 (-) connects
to the internal power bus.
Do not connect anything to terminals 0 and 1. These are
reserved terminals.

4. Connect the PROFIBUS connector plug to the D-shell on the

adapter. Tighten the screws to secure.

Terminal

Description

Notes

0

No connection

Reserved

1

No connection

2

Chassis Ground

3

Chassis Ground

4

Common

5

Common

6

Voltage Input

Apply 12/24V dc. Connects to
the internal power bus.

7

Voltage Input

CHAS GND

NC

NC

C

V

CHAS GND

V dc

C

V

0

2

4

6

1

3

5

7

This dc supply will be
connected to the
internal power bus.

12/24V dc

Do not connect 120/240V ac
power to this supply.

NC = No Connection
CHAS GND = Chassis Ground
C = Common
V = Supply