Appendix a, Specifications, Specifications - 1734-apb profibus adapter module – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 63: Communication interface specifications, Appendix

Advertising
background image

1

Publication 1734-UM005B-EN-P - June 2001

Appendix

A

Specifications

Specifications - 1734-APB PROFIBUS Adapter Module

Communication Interface Specifications

Expansion I/O Capacity

Up to 13 modules (13 times 75mA = 0.975, just under the limit
of 1.0A). The actual number of modules can vary. Add up the
current requirements of the modules you want to use to make
sure they do not exceed the amperage limit of the 1734-ADN.
(Note: Total expansion up to 63 modules - 13 modules maximum
with 1734-APB - add 1734-EP24DC modules for an additional 17
modules (or less based on current requirements), up to 63
module maximum)
Cat. No.

PointBus Current Requirements

1734-IB2

75mA

1734-IB4

75mA

1734-IV2

75mA

1734-IV4

75mA

1734-OB2E

75mA

1734-OB4E

75mA

1734-OW2

80mA

1734-IE2C

75mA

1734-OE2C

75mA

1734-IE2V

75mA

1734-OE2V

75mA

1734-IA2

75mA

1734-IM2

75mA

1734-OA2

75mA

1734-IJ2

160mA

1734-IK2

160mA

1734-IR2

220mA

1734-IT2

175mA

1734-VHSC5

180mA

1734-VHSC24

180mA

Module Location

Starter module - left side of 1734 system

Power Supply Specifications

Power Supply

Note: In order to comply with CE Low Voltage Directives (LVD),
you must use either a NEC Class 2, a Safety Extra Low Voltage
(SELV) or a Protected Extra Low Voltage (PELV) power supply to
power this adapter.A SELV supply cannot exceed 30V rms, 42.4V
peak or 60V dc under normal conditions and under single fault
conditions. A PELV supply has the same rating and is connected
to protected earth.

Input Voltage Rating

24V dc nominal
10-28.8V dc range

Field Side Power Requirements 24V dc (+20% = 28.8V dc maximum) @ 400mA maximum

Inrush Current

6A maximum for 10ms

PointBus Output Current

1A maximum @ 5V dc ±5% (4.75 - 5.25)

Input Overvoltage Protection

Reverse polarity protected

Interruption

Output voltage will stay within specifications when input drops
out for 10ms at 10V with maximum load.

Specifications continued on next page.

Advertising