1734-ob4e electronically protected output module, Product code: 0086h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 71: Configuration data, Diagnostic data, Product code: 0086h data map

Advertising
background image

Publication 1734-UM005B-EN-P - June 2001

Default Data Maps B-7

1734-OB4E Electronically
Protected Output Module

Product Code: 0086h

Data Map:

Output size: 1 bytes; Input size: 0 byte

Configuration Data:

Default: H10 (Default: Fault/Idle value = OFF, No load, Latch)

Diagnostic Data

Possible Error Codes:

7

6

5

4

3

2

1

0

)Produces (Rx)

No produced data

Consumes (Tx)

Not used

CH3
state

CH2
state

CH1

state

CH0

state

Where: CH0, CH1, CH2, CH3; 0 = OFF, 1 = ON

7

6

5

4

3

2

1

0

Reserved

RM

NL

IV

IA

FV

FA

Meaning of bits described below

FA = Fault Action

FV = Fault Value

Value

Definition

Value Definition

0

Fault Value

0

OFF

1

Hold Last State

1

ON

IA = Idle Action

IV = Idle Value

Value

Definition

Value Definition

0

Idle Value

0

OFF

1

Hold Last State

1

ON

NL = No Load Enble

RM = Reset Mode

Value

Definition

Value Definition

0

Disable

0

Latch

1

Enable

1

Auto Retry

Code

Error Type

4

Overload

6

Wire Break

16

Module incorrect or missing. Reported on channel 0, applies to whole module.