1734-ib4 sink input module, Product code: 0082h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual
Page 67: Configuration data, Diagnostic data, Product code: 0082h data map
Advertising
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-3
1734-IB4 Sink Input Module
Product Code: 0082h
Data Map:
Output size: 0 bytes; Input size: 1 byte
Configuration Data:
Filter Values
Default: H00 (1ms)
Diagnostic Data
Possible Error Codes:
7
6
5
4
3
2
1
0
Produces (Rx)
Not used
CH3
state
CH2
state
CH1
state
CH0
state
Consumes (Tx)
No consumed data
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON
7
6
5
4
3
2
1
0
Reserved
Filter
Meaning of bits described below
Value
Definition
00
1ms
01
0.33ms
10
3ms
11
10ms
Error Code
Error Type
16
Module incorrect or missing. Reported on channel 0 and applies to
whole module.