1734-ib2 sink input module, Product code: 0081h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 66: Configuration data, Diagnostic data, Product code: 0081h data map

Advertising
background image

Publication 1734-UM005B-EN-P - June 2001

B-2 Default Data Maps

1734-IB2 Sink Input Module

Product Code: 0081h

Data Map:

Output size: 0 bytes; Input size: 1 byte

Configuration Data:

Filter Values

Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:

7

6

5

4

3

2

1

0

Produces (Rx)

Not used

CH1

state

CH0

state

Consumes (Tx)

No consumed data

Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON

7

6

5

4

3

2

1

0

Reserved

Filter

Meaning of bits described below

Value

Definition

00

1ms

01

0.33ms

10

3ms

11

10ms

Error Code

Error Type

16

Module incorrect or missing. Reported on channel 0 and applies to
whole module.