Chapter 5, Grouped mode, In this chapter – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 55: General, How to configure the adapter for grouped mode, Configuration example, Chapter summary and what’s next, Insert modules adjacent to each other, Modules must be in the same module family, A maximum of 8 channels (1 byte) per group

Advertising
background image

1

Publication 1734-UM005B-EN-P - June 2001

Chapter

5

Grouped Mode

In This Chapter

In this chapter, you will learn about:

General

In order to use master memory most effectively, and reduce data
transfer between the POINT I/O adapter and the master, you can
group several modules in a single byte.

To configure the adapter for grouped mode you must:

1. insert modules adjacent to each other

2. Modules must be in the same module family

Groups may exist as follows:

1734-IB2, 1734-IV2, 1734-IM2 and 1734-IA2 can be grouped
together

1734-IB4 and 1734-IV4 can be grouped together

1734-OW2, 1734-OA2 and 1734-OX2 can be grouped together

The following modules cannot be grouped with any other
module type:

1734-OB2E can only be grouped with 1734-OB2E modules

1734-OB4E can only be grouped with 1734-OB4E modules

3. A maximum of 8 channels (1 byte) per group

4. Modules in a single byte will have the configuration of the first

module in the group. (Exception: Extended diagnostics can be
enabled/disabled on a per module basis.)

For more information about:

See page:

General

5-1

How to Configure the Adapter for Grouped Mode

5-2

Configuration Example

5-3

Chapter Summary and What’s Next

5-4