1734-ow2 relay sink/source output module, Product code: 0087h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 72: Configuration data, Diagnostic data, Product code: 0087h data map

Advertising
background image

Publication 1734-UM005B-EN-P - June 2001

B-8 Default Data Maps

1734-OW2 Relay
Sink/Source Output Module

Product Code: 0087h

Data Map:

Output size: 1 bytes; Input size: 0 byte

Configuration Data:

Default: H00 (Default: Fault/Idle value = OFF)

Diagnostic Data

Possible Error Codes:

7

6

5

4

3

2

1

0

)Produces (Rx)

No produced data

Consumes (Tx)

Not used

CH1

state

CH0

state

Where: CH0 = output channel 0, CH1 = output channel 1; 0 = OFF, 1 = ON

7

6

5

4

3

2

1

0

Reserved

IV

IA

FV

FA

Meaning of bits described below

FA = Fault Action

FV = Fault Value

Value

Definition

Value Definition

0

Fault Value

0

OFF

1

Hold Last State

1

ON

IA = Idle Action

IV = Idle Value

Value

Definition

Value Definition

0

Idle Value

0

OFF

1

Hold Last State

1

ON

Code

Error Type

16

Module incorrect or missing. Reported on channel 0, applies to whole module.

Advertising