1734-ie2v analog voltage input module, Product code: 0018h, Data map – Rockwell Automation 1734-APB Point I/O Profibus Adapter Module User Manual

Page 76: Configuration data, B-12, Product code: 0018h data map

Advertising
background image

Publication 1734-UM005B-EN-P - June 2001

B-12 Default Data Maps

1734-IE2V Analog Voltage
Input Module

Product Code: 0018h

Data Map:

Output size: 0 Words; Input size: 2 Words

Configuration Data:

7

6

5

4

3

2

1

0

Produces (Rx)

Input Channel 0

Input Channel 1

Consumes (Tx)

No consumed data

7

6

5

4

3

2

1

0

Reserved

DF

AD

R

Notch Filter NF

Engineering Units Low (high byte)

Default value = 06h

Engineering Units Low (low byte) Default value = 66h

Engineering Units High (high byte)

Default value = 3Fh

Engineering Units High (low byte) Default value = FFh

Low Alarm Threshold (high byte) Default value = 0Ch

Low Alarm Threshold (low byte) Default value = 29h

High Alarm Threshold (high byte) Default value =40h

High Alarm Threshold (low byte) Default value = A3h

Meaning of bits described below

NF = Notch Filter Values

Value

Definition

00

50Hz

01

60Hz (default)

10

250Hz

11

500Hz

AD = Alarm Disable

R = Range

Value

Definition

Value

Definition

0

Enable (default)

0

-10 to +10V (default)

1

Disable

1

0 to +10V