Chapter 2
Quick Start for Experienced Users

2–4

To wire the network, a 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each
end (scanner and last physical device) of the network. The size of the resistor depends on the baud rate and extended
node capability, as shown below:

Baud Rate

Maximum Cable Distance

(Belden 9463)

Resistor Size

Us n

xten e

57.6K baud

3048 meters (10,000 feet)

8

W 1

Using Extended

o e apab l t

115.2K baud

1524 meters (5,000 feet)

82

W 1/2 Watt

r

Gr

r

G

Node Capability

230.4K baud

762 meters (2,500 feet)

Brown–Green–Brown–Gold

ot Us n

57.6K baud

3048 meters (10,000 feet)

150

W 1/2 Watt

Not Using

xten e

o e

115.2K baud

1524 meters (5,000 feet)

150

W 1/2 Watt

Brown–Green–Brown–Gold

Extended Node
Capability

230.4K baud

762 meters (2,500 feet)

82

W 1/2 Watt

Gray–Red–Black–Gold

6.

Enter your ladder program.

Reference

Define the application requirements. Write and enter the ladder logic program.

Chapter 6

(Programming)

Chapter 8

(Application

Examples)

7.

Go through the system start-up procedure.

Reference

Power up your system by performing standard start-up procedures as indicated in your processor
manual. No special start-up procedures are required when using the DCM module.