Chapter 4
Module Configuration

4–2

Starting I/O Group Number (SW1-7 and SW1-8)

The starting I/O group number is the first word assigned to the DCM from
the scanner’s image table. The starting I/O group number must be an even
number from 0 to 6 and is dependent upon whether the DCM has been
configured as a full, 3/4, 1/2, or 1/4 rack. The first word transferred is
always the status word for the DCM.

Rack Size

Number of RIO Words Transferred

Total Words

1/4 Logical Rack

1 Status and 1 Data

2

1/2 Logical Rack

1 Status and 3 Data

4

3/4 Logical Rack

1 Status and 5 Data

6

Full Logical Rack

1 Status and 7 Data

8

Reference the table below to set the starting I/O group number.

Starting I/O Group Number

SW1-7

SW1-8

Valid Rack Configuration

0

ON

ON

All

2

ON

OFF

3/4, 1/2, 1/4

4

OFF

ON

1/2, 1/4

6

OFF

OFF

1/4

Example of different starting groups:

A

S

S

T

T

U

W O

R

D

Group 0, Word 0

Group 1, Word 1

Group 2, Word 2

Group 3, Word 3

Group 4, Word 4

Group 5, Word 5

Group 6, Word 6

Group 7, Word 7

DCM 2 Rack Size
= 1/2 Rack

R R

In the above image map example, selecting I/O Group Number 2 instructs the scanner
to address Word 2 as the beginning of DCM 2 image. In this example, a half rack is
selected for DCM 2 (using SW2 switches 5 and 6). Since Word 2 is the first word
assigned, it becomes the Status Word.

DCM 1 Rack Size
= 1/4 Rack

DCM 3 Rack Size
= 1/4 Rack

Starting Group 2

Starting Group 0

Starting Group 6

A

S

S

T

T

U

W O

R

D

A

S

S

T

T

U

W O

R

D

Decimal

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Octal

Bit Number:

17 16 15 14 13 12 11 10 7

6

5

4

3

2

1

0

DIP Switch 1 Settings