Network wiring, Chapter 5 installation and wiring, Rio link connector – Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual

Page 41

Advertising
background image

Chapter 5
Installation and Wiring

5–3

A 1/2 watt terminating resistor must be attached across line 1 and line 2 of
the connectors at each end (scanner and last physical device) of the network.
The size of the resistor depends upon the baud rate and extended node
capability, as shown below:

Baud Rate

Terminating Resistor Size

Maximum Cable Distance

(Belden 9463)

Using Extended
Node Capability

All Baud Rates

82

W 1/2 Watt

10,000 feet at 57.6K baud

5,000 feet at 115.2K baud

2,500 feet at 230.4K baud

Not Using

57.6K baud

150

W 1/2 Watt

3048 meters (10,000 feet)

Not Using

Extended Node

apab l t

115.2K baud

150

W 1/2 Watt

1524 meters (5,000 feet)

xten e

o e

Capability

230.4K baud

82

W 1/2 Watt

762 meters (2,500 feet)

Terminating
Resistor

Terminating
Resistor

RIO Scanner

1747-DCM
Direct Communication Module

1747-DCM
Direct Communication Module

Line 1 – Blue

Shield – Shield

Line 2 – Clear

Line 1 – Blue

Shield – Shield

Line 2 – Clear

Line 1 – Blue

Shield – Shield

Line 2 – Clear

DCM

RIO Link
Connector

COMM

FAULT

CONFIGURATION

RACK SIZE

1/4 1/2 3/4 1

RACK ADDR

FIRST I/O GROUP

0 2 4 6

DATA RATE (K B/S)

57.6 115.2 230.4

LINE 1 _______

SHIELD ______

LINE 2 _______

1747–DCM

SW2

SW1

O

N

1

2

3

4

567

8

O

N

1

2

3

4

567

8

I/O

GROUP

(LSB)

RACK

ADDRESS

(MSB)

RACK

SIZE

DATA
RATE

X
X

LAST RACK

CLR ON FLT

Network Wiring