Chapter 4
Module Configuration

4–6

Rack Size (SW2-5 and SW2-6)

The logical rack size allocates image space in the scanner for each DCMs I/O
data. The DCM allows 1/4, 1/2, 3/4, and full rack addressing. SW2 switches
5 and 6 define the rack size.

Rack Size

SW2-5

SW2-6

1/4 Logical Rack

ON

ON

1/2 Logical Rack

ON

OFF

3/4 Logical Rack

OFF

ON

Full Logical Rack

OFF

OFF

Important: The DCM image cannot cross logical rack boundaries.

Therefore, as an example, configuring the module for 1/2
logical rack with starting group 6 will cause a configuration
error. Refer to Starting I/O Group Number on page 4–2.

Last Rack (SW2-4)

Switch 4 of SW2 must be set to the OFF position if the DCM shares its
logical rack with at least one other adapter and has been assigned the highest
I/O group number in that logical rack.

Last Rack

SW2-4

Yes

OFF

No

ON

Remote I/O Scanner

SLC Output Image (to the PLC)

Module 2 Configured As:
Logical Rack Address 1
I/O Group 2
Module Rack Size 1/4

Module 1 Configured As:
Logical Rack Address 1
I/O Group 0
Module Rack Size 1/4

Module 3 Configured As:
Logical Rack Address 1
I/O Group 4
Module Rack Size 1/4

Module 4 Configured As:
Logical Rack Address 1
I/O Group 6
Module Rack Size 1/4

Direct Communications Module 1

Octal

15 14 13 12 11 10 7

6

5

4

3

2

1

0

Group 0, Word 0

Group 1, Word 1

Group 2, Word 2

Group 3, Word 3

Group 4, Word 4

Group 5, Word 5

Group 6, Word 6

Group 7, Word 7

17 16

Module 1

Module 2

Module 3

Module 4

Module 4 is the last device in the logical rack.

Because Module 4 is the last RIO adapter
in a logical rack shared by other adapter(s),
SW2 switch 4 must be in the OFF position.

Logical
Rack 1

13 12 11 10

9

8

7

6

5

4

3

2

1

0

15 14

Decimal

Bit Number:

DIP Switch 2 Settings