Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual

Page 52

Advertising
background image

Chapter 6
Programming

6–10

RIO Scanner Input Status and DCM/SLC Output Status

Using the Logical OR Bit

Whenever any of the status word bits (except the User Status Flag bit) are
set, the Logical OR bit is set. Using an Examine If Open (XIO) instruction
examining the Logical OR bit (word 0, bit 8 for SLC; word 0, bit 10 for
PLC-5) in your ladder logic, you could inhibit any outputs or processors
when this bit is set.

] [

I:3.1

00

]/[

I:3.0

08

( )

O:1.0

00

SLC Rung
to Monitor

PLC-5 Status Bit 08