8 - application examples, Basic example, Application examples – Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual

Page 55

Advertising
background image

8

Chapter

8–1

Application Examples

This chapter provides and examines two applications of the DCM.

basic example

supplementary example

In the following application, the 1747-DCM in the remote rack 2 will
monitor the 1747-SN data from the local rack 1. The program examples in
both local and remote rack CPUs consist of 1 rung each. When input I:1/0 is
enabled in the local rack, the output O:3.1/0 condition is transferred to the
1747-DCM input image via the 1747-SN output image. This condition
enables O:2/0 in the remote rack output card.

RIO

(Belden 9463)

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

Rack 1

Rack 2

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

= slot not used

SLC 5/02

Input

Output

SN

P2

Output

DCM

SLC 5/01

P2

Input Switch

1747-SN Module Configuration

Baud Rate =

57.6K baud

G-file Size =

3 words

G-File

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word 0

Reserved

Word 1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

= Starting Address 0

Word 2

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

= 1/4 Rack Size

See SN manual for further details on configuration.

Basic Example

Advertising