Chapter 7
Troubleshooting

7–2

If LED is:

Cause:

Corrective action:

On

Normal State

No action required.

Blinking

RIO scanner’s processor

in Program/Test Fault

Mode

Check for RIO scanner’s processor error, correct
condition, and cycle power to DCM.

RIO scanner’s processor

not connected to scanner

Check that the scanner is properly installed in rack (RIO
scanner’s processor–2, #3).

Off

RIO scanner’s processor

rack inhibited

Check RIO scanner’s processor rack integrity, correct any
problem, and cycle power to DCM.

No communication

Check that the baud rate of the DCM matches the baud
rate of the scanner.

No communication

between RIO scanner’s

processor and DCM

Check cable connections from the RIO scanner’s
processor or scanner to the DCM.

processor and DCM

Check that the DCM connector is properly installed.

Troubleshooting Using the
COMM LED (Green)