Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual

Page 37

Advertising
background image

Chapter 4
Module Configuration

4–7

Clear On Fault (SW2-3)

!

ATTENTION: Before setting SW2-3 to ON, make sure that
holding all DCM input bits in their last state, in the event a
communication error occurs, does not create an unsafe condition
in the distributed SLC processor.

Clear On Fault

SW2-3

Yes

OFF

No

ON

Turn switch to OFF position if you want the DCM to clear and hold clear all
data bits in its input image table, in the event of an RIO communication
failure or when the supervisory processor enters Program/Test/Fault Mode.
Status bits will not be cleared.

Turn switch to ON position if you want the DCM to hold all input data bits in
their last state when an RIO communication failure occurs or when the
supervisory processor enters Program/Test/Fault Mode.

Data Rate (SW2-1 and SW2-2)

Data Rate

SW2-1

SW2-2

Cable Length (Belden 9463)

57.6K baud

ON

ON

3048 meters (10,000 feet)

115.2K baud

ON

OFF

1524 meters (5,000 feet)

3

b

OFF

ON

7

r

f

230.4K baud

OFF

OFF

762 meters (2,500 feet)