Rockwell Automation 1747-DCM,D17476.8 Direct Communication Module User Manual
Page 37
Chapter 4
Module Configuration
4–7
Clear On Fault (SW2-3)
!
ATTENTION: Before setting SW2-3 to ON, make sure that
holding all DCM input bits in their last state, in the event a
communication error occurs, does not create an unsafe condition
in the distributed SLC processor.
Clear On Fault
SW2-3
Yes
OFF
No
ON
Turn switch to OFF position if you want the DCM to clear and hold clear all
data bits in its input image table, in the event of an RIO communication
failure or when the supervisory processor enters Program/Test/Fault Mode.
Status bits will not be cleared.
Turn switch to ON position if you want the DCM to hold all input data bits in
their last state when an RIO communication failure occurs or when the
supervisory processor enters Program/Test/Fault Mode.
Data Rate (SW2-1 and SW2-2)
Data Rate
SW2-1
SW2-2
Cable Length (Belden 9463)
57.6K baud
ON
ON
3048 meters (10,000 feet)
115.2K baud
ON
OFF
1524 meters (5,000 feet)
3
b
OFF
ON
7
r
f
230.4K baud
OFF
OFF
762 meters (2,500 feet)