Replacement fuse recommendations – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 13

Advertising
background image

SLC 500 Digital I/O Modules 13

Publication 1746-IN027D-EN-P - December 2012

The following table defines operation of all SLC 500 processors in the case of a blown fuse in
1746-OBP16, 1746-OVP16, and 1746-OAP12 modules.

Recovery From Blown Fuse/Processor Fault/Processor Shutdown

Processor operation will stop under the following conditions:

• The output module fuse blows due to a short circuit.
• JP1 is set to the Processor Faults position (pins 2 and 3 connected).

If the above conditions occur, the following procedures should be used for recovery.

1. Follow fuse replacement procedures described on

page 14

.

2. Clear the processor major fault bit S:1/13.
3. Clear processor status file S:6 major error code (optional).
4. Return the processor to Run mode.

For additional information on processor fault codes and clearing processor fault bits, refer to the
following user manuals:

• Your programming device’s reference manual
• HHT User Manual, publication 1747-NP002

• Chapter 28, Troubleshooting Fault

• Chapter 29, Understanding the Fault Routine

Replacement Fuse Recommendations

Use the following replacement fuses:

• 1746-OBP16 and 1746-OVP16 modules – Littelfuse #322010,10A or #332010,10A.

This fuse is required to maintain UL/CSA rating. Replacement Fuse Kit is catalog
number
1746-F8 (five fuses per kit).

• 1746-OAP12 module - Use SAN-O HQ 6.3A for replacement. This fuse is required to

maintain UL/CSA rating. Replacement Fuse Kit is catalog number
1746-F9 (five fuses per kit).

Processor Operation After a Blown Fuse (1746-OBP16, 1746-OVP16, and
1746-OAP12 modules)

JP1 Set to Processor Continues

JP1 Set to Processor Faults

No error. Processor continues with 1746-OBP16
and 1746-OVP16 outputs de-energized.
1746-OAP12 outputs, on the same common as the
blown fuse, are de-energized.

Nonrecoverable error. Processor operations stop and all
outputs reset to OFF.