SLC 500 Digital I/O Modules 39

Publication 1746-IN027D-EN-P - December 2012

Voltage, operating (V DC)

10…30 (source)

20.4...26.4 (source)

Backplane current
consumption

5V DC

0.046 A

0.135 A

0.250 A

24V DC

0.0 A

Signal delay, max resistive load

On = 1.0 ms

(7)

Off = 2.0 ms

On = 1.0 ms

(7)

Off = 2.0 ms

On = 0.1 ms

(7)

Off = 1.0 ms

Off-state leakage, max

(1)

1 mA

Load current, min

1 mA

Continuous current per point

(2)(3)

2.0 A @ 0…60 °C (140 °F)

2.0 A @ 0…60 °C (140 °F)

1.5 A @ 30 °C (86 °F)
1.0 A @ 60 °C (140 °F)

Continuous current per module

12.0 A @ 0…60 °C (140 °F)

8.0 A @ 0…60 °C (140 °F)

6.4 A @
0...60 °C (32...140 °F)

On-state voltage drop, max

1.0V @ 2.0 A

1.0V @ 2.0 A

1.0V @ 1.0 A

Surge current per point

(4)

4.0 A for 10 ms

4.0 A for 10 ms

4.0 A for 10 ms

Surge current per module

(4)

24.0 A for 10 ms

32.0 A for 10 ms

32.0 A for 10 ms

Electronic protection

Yes

No

No

(1)

To limit the effects of leakage current through solid state outputs, a loading resistor can be connected in parallel with your load. For transistor
outputs, 24V DC operation, use a 5.6 K

Ω, 1/2 W resistor.

(2)

Recommended surge suppression: For transistor outputs when switching 24V dc inductive loads, use a 1N4004 diode reverse-wired across the
load (also see footnote 3). Refer to the SLC 500 Modular Hardware Style User Manual, publication

1747-UM011

, for more information on surge

suppression.

(3)

Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B
and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this is
the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.

(4)

Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).

(5)

Removable terminal block.

(6)

Use the following ID Code when configuring your system with programming software or the HHT: 1746-OB6EI = 2619, 1746-OBP8 = 2721 and
1746-OBP12 = 2921.

(7)

Fast turn-off modules (1746-OB6EI, 1746-OBP8 Series B and later, 1746-OB16E Series B and later, 1746-OBP16, and 1746-OVP16) provide fast
OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin
100-B110 (24W sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.

(8)

An external fuse can be used to protect this module from short circuits. Recommended fuse is SANO MQ4-3.15A, 5 x 20 mm.

(9)

A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.

(10)

Certified for Class 1, Division 2 hazardous location by CSA.

Specifications – 1746-OB6EI, 1746-OBP8, and 1746-OBP16

Attribute

Value

1746-OB6EI

(5)(6)

1746-OBP8

(5)(6)(8)

1746-OBP16

(5)(6)(9)(10)