Input Modules Heat Dissipation

Catalog Numbers

Watts per Point

Minimum Watts

Total Watts

1747-IA4

0.27

0.175

1.30

1746-IA8

0.27

0.250

2.40

1746-IA16

0.27

0.425

4.80

1746-IB8

0.20

0.250

1.90

1746-IB16

0.20

0.425

3.60

1746-IC16

0.22

0.425

3.95

1746-IG16

0.02

0.700

1.00

1746-IH16

0.32

0.217

5.17

1746-IM4

0.35

0.175

1.60

1746-IM8

0.35

0.250

3.10

1746-IM16

0.35

0.425

6.00

1746-IN16

0.35

0.425

6.00

1746-ITB16

0.20

0.425

3.60

1746-ITV16

0.20

0.425

3.60

1746-IV8

0.20

0.250

1.90

1746-IV16

0.20

0.425

3.60

Output Modules Heat Dissipation

Catalog Numbers

Watts per Point

Minimum Watts

Total Watts

1746-OA8

1.000

0.925

9.00

1746-OA16

0.462

1.850

9.30

1746-OAP12

1.000

1.850

10.85

1746-OB6EI

0.440

0.230

2.90

1746-OB8

0.775

0.675

6.90

1746-OB16

0.388

1.400

7.60

1746-OB16E

0.150

0.675

3.07

1746-OBP8

0.300

0.675

3.08

1746-OBP16

0.310

1.250

6.26

1746-OG16

0.033

0.900

1.50