Relay contact ratings – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 43

Advertising
background image

SLC 500 Digital I/O Modules 43

Publication 1746-IN027D-EN-P - December 2012

Relay Contact Ratings

Voltage, operating

5V DC

5...125

24V DC

5...265

Signal delay, max resistive load

On = 10.0 ms
Off = 10.0 ms

Backplane current
consumption

5V DC

0.045 A

0.085 A

0.170 A

0.085 A

24V DC

0.045 A

0.090 A

0.180 A

0.090 A

Off-state leakage, max

0 mA

Load current, min

10 mA @ 5V DC

Continuous current per point

(1)

See

Relay Contact Ratings on page 43

.

Continuous current per module

8.0 A AC
8.0 A /Common

16.0 A AC
8.0 A /Common

16.0 A AC
8.0 A /Common

(4)

(1)

Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication

1747-UM011

.

Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.

(2)

Certified for Class 1, Division 2 hazardous location by CSA.

(3)

Removable terminal block.

(4)

The continuous current per module must be limited so the module power does not exceed 1440V A.

Relay Contact Ratings – 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC

Voltages

Amperes

(1)

(1)

The continuous current per module must be limited so the module power does not exceed 1440V A.

Amperes

(1)

Continuous

Volt-Amperes

Make

Break

Make

Break

Volts (AC), max

120

15

1.5

2.5

1800

180

240

7.5

0.75

Volts (DC), max

125

0.22

(2)

(2)

For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28VA by the applied DC
voltage. For example, 28V A/48V DC = 0.58 A. For DC voltage applications less than 14V, the make/break ratings for relay contacts
cannot exceed 2 A.

1.0

28

24

1.2

(2)

2.0

28

Specifications – 1746-OW4, 1746-OW8, 1746-OW16, and 1746-OX8

Attribute

Value

1746-OW4

(2)

1746-OW8

(2)

1746-OW16

(2)(3)

1746-OX8

(2)(3)