SLC 500 Digital I/O Modules 41

Publication 1746-IN027D-EN-P - December 2012

(8)

Fast turn-off modules (1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series B and later, 1746-OBP16, and 1746-OVP16) provide fast
OFF delay for inductive loads. Comparative OFF delay times for 1746-OB8/1746-OV8 and fast turn-off modules; when switching Bulletin
100-B110 (24Ws sealed) contactor, are: 1746-OB8/1746-OV8 OFF delay = 152 ms; fast turn-off modules OFF delay = 47 ms.

(9)

Fast off delay for inductive loads is accomplished with surge suppressors on the 1746-OB6EI, 1746-OBP8 series B and later, 1746-OB16E series
B and later, 1746-OBP16, and 1746-OVP16 modules. A suppressor at the load is not needed unless another contact is connected in series. If this
is the case, a 1N4004 diode should be reverse wired across the load. This defeats the fast turn-off feature.

(10)

Surge current = 32 A per module for 10 ms.

ATTENTION: A transient pulse occurs in transistor outputs when the external DC supply
voltage is applied to the output common terminals (for example, via the master control relay).
This can occur regardless of the processor having power or not. For most applications, the
energy of this pulse is not sufficient to energize the load.

Refer to the SLC 500 Modular Hardware Style User Manual, publication

1747-UM011

, for more

information on transient pulses and guidelines to reduce inadvertent processor operation.

Specifications – 1746-OG16

Attribute

Value

(1)

(1)

Removable terminal block.

Voltage category

5V DC TTL Signal Input (sinking)

Number of outputs

16

Points per common

16

Voltage, operating (V DC to DC COM)

4.5...5.5V DC

(2)

50 mV peak to peak ripple, max.

(2)

TTL outputs are inverted (0...0.4V DC = low voltage = True = ON). Use a NOT instruction in your
ladder program to convert to traditional True = High logic.

Backplane current
consumption

5V DC

0.180 A

24V DC

0.0 A

Signal delay, max resistive load

On = 0.25 mA
Off = 0.50 mA

Off-state voltage

4.5...5.5V DC

Off-state leakage, max

0.1 mA

Load current, min

0.15 mA

Continuous current per point

24 mA

Advertising