34 SLC 500 Digital I/O Modules

Publication 1746-IN027D-EN-P - December 2012

Specifications – 1746-IV8, 1746-IV16, and 1746-ITV16

Attribute

Value

1746-IV8

1746-IV16

(1)

1746-ITV16

(1)

Voltage category

24V DC signal input (sourcing)

Number of inputs

8

16

16

Points per common

8

16

16

Voltage, operating

10...30V DC (sourcing)

Backplane current
consumption

5V DC

0.050 A

0.085 A

0.085 A

24V DC

0.0 A

Signal delay, max

On = 8 ms
Off = 8 ms

On = 8 ms
Off = 8 ms

On = 0.3 ms
Off = 0.5 ms

(2)

Off-state voltage, max

5.0V DC

Off-state current, max

1 mA

1 mA

1.5 mA

Input current

8 mA @ 24V DC, nom

(1)

Removable terminal block.

(2)

Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms @ 24V DC.

Specifications – 1746-IG16

Attribute

Value

(1)

(1)

Removable terminal block.

Voltage category

5V DC TTL signal input (sourcing)

Number of inputs

16

Points per common

16

Voltage, operating +5V to DC COM

4.5...5.5V DC (sourcing)
50 mV peak to peak ripple (max)

Backplane current
consumption

5V DC

0.140 A

24V DC

0.0 A

Signal delay, max

On = 0.25 ms
Off = 0.50 ms

Off-state voltage

2...5.5 V DC

(2)

(2)

TTL inputs are inverted (-0.2...0.8V DC = low voltage = True = ON). Use a NOT instruction in your ladder program to
convert to traditional True = High logic.

Off-state current, max

4.1 mA

Input current

3.7 mA @ 5V DC, nom

Advertising