Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 37

Advertising
background image

SLC 500 Digital I/O Modules 37

Publication 1746-IN027D-EN-P - December 2012

DC Output Modules

Load current, min

10 mA

Continuous current per point

(3)

1.0 A @ 30 °C (86 °F)
0.50 A @ 60 °C (140 °F)

0.50 A @ 30 °C (86 °F)
0.25 A @ 60 °C (140 °F)

2.0 A @ 30 °C (86 °F)
1.25 A @ 55 °C (131 °F)
1.0 A @ 60 °C (140 °F)

Continuous current per module, max

8.0 A @ 30 °C (86 °F)
4.0 A @ 60 °C (140 °F)

8.0 A @ 30 °C (86 °F)
4.0 A @ 60 °C (140 °F)

9.0 A @ 30 °C (86 °F)
6.8 A @ 55 °C (131 °F)
6.0 A @ 60 °C (140 °F)

On-state voltage drop, max

1.50V @ 1.0 A

1.50V @ 0.50 A

1.2V @ 2.0 A

Surge current per point

(4)

, max

10.0 A for 25 ms

10.0 A for 25 ms

17.0 A for 25 ms

(8)

(1)

Triac outputs turn on at any point in the AC line cycle, and turn off at AC line zero cross.

(2)

To limit the effects of leakage current through solid-state outputs, a loading resistor can be connected in parallel with your load. For 120V AC
operation, use a 15 K

Ω, 2 W resistor. For 240V AC operation, use a 15 KΩ, 5 W resistor.

(3)

Recommended surge suppression: For triac outputs when switching 120V AC inductive loads, use Harris Metal-Oxide Varistor, model number
V220MA2A. Refer to the SLC 500 Modular Hardware Style User Manual, publication

1747-UM011

, for more information on surge suppression.

(4)

Repeatability is once every 1 s at 30 °C (86 °F). Repeatability is once every 2 s at 60 °C (140 °F).

(5)

Removable terminal block.

(6)

A fused common and blown fuse LED indicator are provided on this module. See Fuse Protection and Blown Fuse Diagnostics.

(7)

Use ID Code 2803 when configuring your system with programming software or the HHT.

(8)

Surge current = 35 A per common for 10 ms.

Specifications – 1746-OB8, 1746-OB16, and 1746-OB16E

Attribute

Value

1746-OB8

1746-OB16

(4)

1746-OB16E

(4)(5)

Voltage category

24V DC Signal Output

Number of outputs

8

16

16

Points per common

8

16

16

Voltage, operating (V DC)

10...50 (source)

10...30 (source)

Backplane current
consumption

5V DC

0.135 A

0.280 A

0.135 A

24V DC

0.0 A

Signal delay, max resistive load

On = 1 ms
Off = 1.0 ms

On = 0.1 ms
Off = 1.0 ms

On = 1.0 ms

(6)

Off = 1.0 ms

Off-state leakage, max

(1)

1 mA

Load current, min

1 mA

Specifications – 1746-OA8, 1746-OA16, and 1746-OAP12

Attribute

Value

1746-OA8

1746-OA16

(5)

1746-OAP12

(5)(6)(7)

Advertising