SLC 500 Digital I/O Modules 33

Publication 1746-IN027D-EN-P - December 2012

DC Input Modules

Input current

12 mA @ 240V AC, nom

Inrush current, max

(1)

1.6 A

Inrush current time duration, max

0.5 ms

(1)

An AC input device must be compatible with SLC 500 input circuit inrush current. A current limiting resistor can be used to limit
inrush current; however, the operating characteristics of the AC input-circuit will be affected.

(2)

Removable terminal block.

Specifications – 1746-IB8, 1746-IB16, 1746-ITB16, and 1746-IC16

Attribute

Value

1746-IB8

1746-IB16

(1)

(1)

Removable terminal block.

1746-ITB16

(1)

1746-IC16

(1) (3)

(3)

Typical signal delay for these modules: ON = 0.1 ms, OFF = 0.25 ms @ 24V DC.

Voltage category

24V DC signal input (sinking)

48V DC signal input (sinking)

Number of inputs

8

16

16

16

Points per common

8

16

16

16

Voltage, operating

10...30V DC (sinking)

30...60V DC @ 55 °C (131 °F) sinking
30...55V DC @ 60 °C (140 °F) sinking

Backplane current
consumption

5V DC

0.050 A

24V DC

0.0 A

Signal delay, max

On = 8 ms
Off = 8 ms

On = 8 ms
Off = 8 ms

On = 0.3 ms
Off = 0.5 ms

(2)

(2)

Use ID Code 0509 when configuring your system with programming software or the HHT.

On = 4 ms
Off = 4 ms

Off-state voltage, max

5.0V DC

10.0V DC

Off-state current, max

1 mA

1 mA

1.5 mA

1.5 mA

Input current, nom

8 mA @ 24V DC

4.1 mA @ 48V DC

Specifications – 1746-IM4, 1746-IM8, and 1746-IM16

Attribute

Value

1746-IM4

1746-IM8

1746-IM16

(2)