44 SLC 500 Digital I/O Modules

Publication 1746-IN027D-EN-P - December 2012

Relay Contact Ratings – 1746-OX8

Voltages

Amperes

(1)

(1)

Recommended surge suppression: For relay contact outputs, refer to the SLC 500 Modular Hardware User Manual, publication

1747-UM011

. Connecting surge suppressors across your external inductive load will extend the life of SLC 500 relay contacts.

Amperes

Continuous

(3)

(3)

The continuous current per module must be limited so the module power does not exceed 1440V A.

Volt-Amperes

Make

Break

Make

Break

Volts (AC), max

120

30

3.0

5.0

3600

360

240

15

1.5

Volts (DC), max

125

0.22

(2)

(2)

For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28V A by the applied DC
voltage. For example, 28V A/48V DC = 0.58 A. For DC voltage applications less than 14V, the make/break ratings for relay contacts cannot
exceed 2 A.

1.0

28

24

1.2

(2)

2.0

28