36 SLC 500 Digital I/O Modules

Publication 1746-IN027D-EN-P - December 2012

AC Output Modules

Specifications – 1746-IH16

Attribute

Value

(1)(2)(3)

Voltage category

125V DC signal input (sinking)

Number of inputs

16

Points per common

16

Voltage, operating

Range:
90...146V DC

Points ON Simultaneously, max:
6 @ 146V DC and 30 °C (86 °F)
12 @ 146V DC and 50 °C (122 °F)
14 @ 132V DC and 55 °C (131 °F)
16 @ 125V DC and 60 °C (140 °F)

Backplane current
consumption

5V DC

0.085 A

24V DC

0.0 A

Signal delay, max

On = 9 ms
Off = 9 ms

Off-state voltage, max

20.0V DC

Off-state current, max

0.8 mA

Input current, nom

2.15 mA @ 125V DC

2.25 mA @ 132V DC

(1)

Removable terminal block.

(2)

Use ID Code 0507 when configuring your system with programming software or the HHT.

(3)

If the input module is connected in parallel with an inductive load, use surge suppression across the load to protect
the input module from damage caused by reverse voltage. Refer to the SLC 500 Modular Hardware Style User
Manual, publication

1747-UM011

, for more information on surge suppression.

Specifications – 1746-OA8, 1746-OA16, and 1746-OAP12

Attribute

Value

1746-OA8

1746-OA16

(5)

1746-OAP12

(5)(6)(7)

Voltage category

120/240V AC signal input

Number of outputs

8

16

12

Points per common

4

8

6

Voltage, operating

85...265V AC @ 47...63 Hz

Backplane current
consumption

5V DC

0.185 A

0.370 A

0.370 A

24V DC

Signal delay, max resistive load

(1)

On = 1 ms
Off = 11.0 ms

Off-state leakage, max

(2)

2 mA