Relay contact modules – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 42

Advertising
background image

42 SLC 500 Digital I/O Modules

Publication 1746-IN027D-EN-P - December 2012

Careful wire routing within the enclosure helps cut down electrical noise between I/O lines.
Refer to the SLC 500 Modular Hardware Style User Manual, publication

1747-UM011

, for

recommended wiring procedures for TTL modules.

Limit cable length to 3 m (10 ft) per point for outputs in standard environments.

Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines,
publication

1770-IN041

, for complete information.

Relay Contact Modules

ATTENTION: To avoid potential damage to TTL modules, handle them by the ends of the module,
not metallic surfaces. Electrostatic discharges can damage the module. Take care to prevent
exposure of terminals or components to electrostatic charges.

WARNING: Exposure to some chemicals may degrade the sealing properties of materials used
in the following devices: Relay Epoxy.

It is recommended that the user periodically inspect these devices for any degradation of
properties and replace the module if degradation is found.

Specifications – 1746-OW4, 1746-OW8, 1746-OW16, and 1746-OX8

Attribute

Value

1746-OW4

(2)

1746-OW8

(2)

1746-OW16

(2)(3)

1746-OX8

(2)(3)

Voltage category

AC/DC Relay

Number of outputs

4

8

16

8

Points per common

4

4

8

Individually isolated

Catalog

Relay

1746-OX8

K1…K8

1746-IO4

K1 and K2

1746-IO8

K1…K4

1746-IO12

K1…K6

1746-IO12DC

K1…K6

1746-OW4

K1…K4

1746-OW8

K1…K8

1746-OW16

K1…K16

Advertising