SLC 500 Digital I/O Modules 35
Publication 1746-IN027D-EN-P - December 2012
Careful wire routing within the enclosure helps cut down electrical noise between I/O lines.
Refer to the SLC 500 Modular Hardware Style User Manual, publicatio
recommended wiring procedures for TTL modules.
Limit cable length to 15 m (50 ft) per point for inputs in standard environments.
Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines,
publication
ATTENTION: To avoid potential damage to TTL modules, handle them by the ends of the
module, not metallic surfaces. Electrostatic discharges can damage the module. take care
to prevent exposure of terminals or components to electrostatic charges.
Specifications – 1746-IN16
Attribute
Value
(1)
(1)
Removable terminal block.
Voltage category
24V AC/DC Signal Input
Number of inputs
16
Points per common
16
Voltage, operating
DC
10...30V DC (sinking)
AC
10...30V AC
Backplane current
consumption
5V DC
0.085 A
24V DC
0.0 A
Signal delay, max
DC
On = 15 ms
Off = 15 ms
AC
On = 25 ms
Off = 25 ms
Off-state voltage, max
DC
3.0V DC
AC
3.0V AC
Off-state current, max
DC
1 mA
AC
1 mA
Input current, nom
DC
8 mA @ 24V DC
AC
8 mA @ 24V AC
Input current
0.02 A (AC only)