Publication 1746-IN027D-EN-P - December 2012

Careful wire routing within the enclosure helps cut down electrical noise between I/O lines.
Refer to the SLC 500 Modular Hardware Style User Manual, publication

1747-UM011

, for

recommended wiring procedures for TTL modules.

Limit cable length to 15 m (50 ft) per point for inputs in standard environments.

Refer to Allen-Bradley Programmable Controller Wiring and Grounding Guidelines,
publication

1770-IN041

, for complete information.

ATTENTION: To avoid potential damage to TTL modules, handle them by the ends of the
module, not metallic surfaces. Electrostatic discharges can damage the module. take care
to prevent exposure of terminals or components to electrostatic charges.

Specifications – 1746-IN16

Attribute

Value

(1)

(1)

Removable terminal block.

Voltage category

24V AC/DC Signal Input

Number of inputs

16

Points per common

16

Voltage, operating

DC

10...30V DC (sinking)

AC

10...30V AC

Backplane current
consumption

5V DC

0.085 A

24V DC

0.0 A

Signal delay, max

DC

On = 15 ms
Off = 15 ms

AC

On = 25 ms
Off = 25 ms

Off-state voltage, max

DC

3.0V DC

AC

3.0V AC

Off-state current, max

DC

1 mA

AC

1 mA

Input current, nom

DC

8 mA @ 24V DC

AC

8 mA @ 24V AC

Input current

0.02 A (AC only)