Combination input/output modules – Rockwell Automation 1746-XXXX SLC 500 Digital I/O Modules Installation Instructions User Manual

Page 45

Advertising
background image

SLC 500 Digital I/O Modules 45

Publication 1746-IN027D-EN-P - December 2012

Combination Input/Output Modules

Specifications – 1746-IO4, 1746-IO8, 1746-IO12, and 1746-IO12DC

Attribute

Value

1746-IO4

(1)(2)

(1)

Certified for Class 1, Division 2 hazardous location by CSA.

(2)

See specifications for catalog numbers 1746-IA4 and 1746-OW4. Continuous Current per 1746-IO4 Module is 4.0 A.
Continuous Current per 1746-IO8 Module is 8.0 A.

1746-IO8

(1)(2)

1746-IO12

(1)(3)(4)

(3)

Removable terminal block.

(4)

See specifications for catalog numbers 1746-IA16 and 1746-OW16. Continuous Current per 1746-IO12 Module is 8.0 A.

1746-IO12DC

(3)(5)(6)(7)

(5)

See specification for catalog numbers 1746-IB16 and 1746-OW16. Continuous Current per 1746-IO12DC Module is 8.0 A.

(6)

Certified for Class 1, Division 2 hazardous location by C-UL.

(7)

Use the following ID Code when configuring your system with programming software or the HHT: 1746-IO12DC = 1512.

Points per module

2 inputs
2 outputs

4 inputs
4 outputs

6 inputs
6 outputs

6 inputs
6 outputs

Points per common

2

4

6

6

Voltage category

120V AC

24V DC

Voltage, operating (inputs)

85...132V AC

10...30V DC

Voltage category (outputs)

100/120V AC Relay contact output

Voltage, operating (outputs)

5...265V AC
5...125V DC

Backplane current
consumption

5V DC

0.030 A

0.060 A

0.090 A

0.080 A

24V DC

0.025 A

0.045 A

0.070 A

0.060 A

TIP

For combination I/O modules 1746-IO4, 1746-IO8, 1746-IO12 and 1746-IO12DC):

The first several seconds of any powerup or when power is applied to a rack that is
not under processor control, the output LED indicators of the combination input and
output modules in the rack will be illuminated.

Racks are not under processor control if one of the following conditions exist:

• Modular Hardware Style (only): Processor is absent from the rack or the rack

interconnect cable is not properly connected.

• Modular Hardware Style and Fixed Hardware Style: The processor does not have the

firmware PROM installed or the processor is not functioning properly.