Mount the 2706-p22r display, Mount the 2706-p22r display -23, Panel cutout dimensions for 2706-p22r display -23 – Rockwell Automation 2706-P42_P43_P44_P72_P74_P92_P94 InView Marquee Message Display User Manual User Manual

Page 31

Advertising
background image

Publication 2706-UM016D-EN-P - March 2006

Install InView Marquee Message Display 1-23

Mount the 2706-P22R
Display

The following provides panel cutout dimensions and overall
dimensions for the InView P22R panel mount display.

The InView P22R mounts in a custom panel or enclosure. When it is
properly installed, the faceplate provides a NEMA Type 12, 13, and
4X(indoor) rating.

To mount the display:

1. Cut and drill the appropriate mounting holes in the enclosure or

panel.

Refer to Panel Cutout Dimensions for 2706-P22R Display on
page 1-23

2. Remove the six mounting nuts and washers from the hardware

bag provided with the display.

3. Position the InView Display in the panel or enclosure mounting

hole.

4. Install washers and nuts and alternately tighten the nuts to a

torque of 0.904 Nm (8 lb-in).

Panel Cutout Dimensions for 2706-P22R Display

TIP

InView P22R mounting and panel cutout are
identical to DL40 Plus, DL40, DL20 and DL10 two
line displays.

Cutout 345.9 (13.62)

Cutout
173.0 (6.81)

98.4
(3.88)

352.3 (13.87)

Cutout
88.9
(3.50)

176.1 (6.94)

4.8 (0.19)

4.8 (0.19)

6.4 (0.25)
Diameter
Hole
6 places

2706-P22R Display

All dimensions are in millimeters (inches)