InView Protocol 4-17

the result. The error check byte is done from the address up to the
data field.

The following is an example of how to calculate the LRC in a Modbus
ASCII transmission.

Example of LRC Calculations

Examples of Modbus ASCII
Functions

The following sections show examples of Modbus ASCII protocol
Query/Response transmissions to/from a display for each command
instruction listed above. Modbus ASCII will write/read to the holding
registers in the display. These registers are in the 40000 range. When
writing to register 40101, 40001 is dropped from the address leaving
100 (0x64). The following example shows the transmission of data to
holding register 40102 in all displays. The display adds 40001 to the
starting address upon receiving the transmission before updating the
appropriate holding register.

Beginning
of Frame

ADDR

FUNC

H.O.

ADDR

L.O.

ADDR

DATA

LRC

Error

EOF

Ready to
rec. resp

05

06

00

1F

0264

70

CR

LF

Modbus ASCII Transmission

Message

Transmitted Bytes

Binary

Address

05

0000 0101

Function

06

0000 0110

Start Add H.O.

00

0000 0000

Start Add L.O.

1F

0001 1111

Data H.O.

02

0000 0010

Data L.O.

64

0110 0100

Sum

90

1001 0000

1's Complement

0110 1111

+1

+0000 0001

2's Complement

0111 0000

Transmitted as

70