6

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

Chapter 2 Discrete and Analog Expansion I/O Features

The 2085-IA8, 2085-IM8, 2085-IQ16 and 2085-IQ32T modules update the
controller with new data whenever an input point transitions from On to Off and
Off to On.

On to Off and Off to On filter times can be adjusted through the Connected
Components Workbench software. These filters improve noise immunity within
a signal. A larger filter value affects the length of delay times for signals from these
modules.

You can select from a series of operational ranges for each channel. The range
designates the minimum and maximum signals that are detectable by the module.

Discrete Output

Output modules may be used to drive a variety of output devices. Typical output
devices compatible with the outputs include:

• motor starters
• solenoids
• indicators

Follow these guidelines when designing a system.

• Make sure that the outputs can supply the necessary surge and continuous

current for proper operation. (See

Specifications on page 45

for more

information.)

• Make sure that the surge and continuous current are not exceeded. Damage

to the module could result. When sizing output loads, check the
documentation supplied with the output device for the surge and
continuous current needed to operate the device. The Micro800 standard
digital outputs are capable of directly driving the Micro800 standard
digital inputs.

Analog Expansion I/O
Features

This section pertains to the following Micro800 analog expansion I/O modules:

TIP

User-configurable options are not available in Connected Components
Workbench for discrete output modules.

IMPORTANT

On controller minor and major fault, all output channels are de-energized.

Micro800 Expansion I/O Modules

Catalog

Type

Description

2085-IF4

Analog

4-channel, 14-bit isolated

(1)

voltage/current input

2085-IF8

Analog

8-channel, 14-bit isolated

(1)

voltage/current input

Advertising