Chapter 5 Configure Your Expansion I/O Module

2085-IF4 and 2085-IF8

For the analog input modules, 2085-IF4 and 2085-IF8, you can configure
properties such as input range, format, filter and alarm limits for each individual
channel.

Configuration Parameters for 2085-IF4 and 2085-IF8

Configuration
Property

What to do

Description

Enable Channel

Select or deselect the
checkbox. The box is selected
by default.

Enable or disable a channel through this
checkbox. By default, each channel is
enabled.

Minimum-Maximum
Input Range

Choose from a range of
values:

0…20 mA

4…20 mA (default)

-10…10 V

0…10 V

Defines the input mode for the channel as
either voltage or current, with current as
default mode.

Data format

Select from the following
options:

Raw/Proportional Data

Engineering Units (default)

Percent Range

See

Data formats on page 7

for detailed

information.

Input filter

Choose from the following
values:

See

Input Filter on page 9

for detailed

information.