The following table shows the default values of the High/Low Clamps (in the
order of low clamp value followed by the high clamp value) for the respective
type/range when they are first enabled. You can change these values (within their
full range) according to your application.

Specialty Module 2085-IRT4 Temperature Input Module

The 2085-IRT4 module lets you configure a sensor type for each of four input
channels that linearizes analog signal into a temperature value.

Sensor Type

The following Thermocouple and RTD sensor types are supported by the
2085-IRT4 expansion I/O module.

Default Range of High Clamp/Low Clamp Values

Data Format

0…20 mA

4…20 mA

-10…10V

0…10V

Raw/Proportional Data

-32768, 29647

-29822, 29086

-31207, 31207

-32768, 29647

Engineering Units

0, 20000

4000, 20000

-10000, 10000

0, 10000

Percent Range

0, 10000

0, 10000

Not supported

0, 10000

Supported Thermocouple Types and mV Range

Sensor Range

Range

B

300…1800 °C

(572…3272 °F)

C

0…2315 °C

(32…4199 °F)

E

-270…1000 °C

(-454…1832 °F)

J

-210…1200 °C

(-346…2192 °F)

K

-270…1372 °C

(-454…2502 °F)

TXK/XK (L)

-200…800 °C

(-328…1472 °F)

N

-270…1300 °C

(-454…2372 °F)

R

-50…1768 °C

(-58…3214 °F)

S

-50…1768 °C

(-58…3214 °F)

T

-270…400 °C

(-454…752 °F)

mV

0…100 mV

Supported RTD Types and Ohms Range

Sensor Range

Range

100

Ω Pt α = 0.00385 Euro

-200…870 °C

(-328…1598 °F)

200

Ω Pt α = 0.00385 Euro

-200…400 °C

(-328…752 °F)

100

Ω Pt α = 0.003916 U.S

-200…630 °C

(-328…1166 °F)

200

Ω Pt α = 0.003916 U.S.

-200…400 °C

(-328…752 °F)