Chapter 3 Wiring Connections

Allen-Bradley 1492 wiring systems are available for connecting the I/O module
to external I/O. These wiring systems include a pre-wired cable available in four
lengths: 0.5m (1.6 feet), 1.0m (3.3 feet), 2.5m (8.2 feet), 5.0m (16.4 feet). An
Interface Module for connecting external devices is also available. Cables are
equipped with keyed connectors at both ends for proper connections. Interface
modules are DIN rail mountable and are available with or without field side
status indicating LEDs. Stick-on labels are provided with the Interface modules to
identify I/O wiring termination points.

Summary

This chapter covered the input and output wiring connections for the different
analog and discrete Micro800 expansion I/O modules.

1492 Cables

Catalog No.

Voltage Drop @ 30 °C

Voltage Drop @ 60 °C

Series C Cables

V DC and DC
Com Wires

(1)

(1) Voltage drop @ maximum rated current of 2 amps per conductor.

Output Channel
Wires

(2)

(2) Voltage drop at maximum rated current of 0.5 amps per output channel.

V DC and DC
Com Wires

Output
Channel Wires

1492-CABLE005H

127 mv

34 mv

144 mv

38 mv

1492-CABLE010H

173 mv

45 mv

196 mv

51 mv

1492-CABLE025H

334 mv

83 mv

388 mv

95 mv

1492-CABLE050H

574 mv

147 mv

686 mv

169 mv