Specifications Appendix A

Off-state current, max

2.5 mA

On-state current, min

5.0 mA @ 74V AC

4.0 mA @ 159V AC

On-state current, max

12.5 mA @ 120V AC

7.0 mA @ 240V AC

Input impedance, max

22.2 k

Ω

Inrush current, max

450 mA

Input filter time
Off to On
On to Off

< 20 ms

IEC type compliance

Type 3

Output Specifications – 2085-OA8

Attribute

2085-OA8

Number of inputs

8

Voltage category

120V/230V AC

Operating voltage range

120…240V AC, 50/60 Hz

Output voltage, min

85V AC

Output voltage, max

240V AC

Off-state leakage current, max

2.5 mA

On-state current, min

10 mA per output

On-state current, max

0.5 A per output

On-state current, per module, max

4 A

Off-state voltage drop, max

1.5V AC @ 0.5 A
2.5V AC @10 mA

Fusing

Not protected. A suitable rating fuse is recommended to
protect outputs.

Output signal delay
Off to On
On to Off

9.3 ms for 60 Hz, 11 ms for 50 Hz
9.3 ms for 60 Hz, 11 ms for 50 Hz

Surge current, max

5 A

2085-OW8 and 2085-OW16 Relay Output Module

Attribute

2085-OW8

2085-OW16

Number of outputs

8, relay

16, relay

Dimensions, HxWxD

28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)

44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)

Shipping weight,
approx.

140 g (4.93 oz)

220 g (7.76 oz)

Wire size

Insulation strip length

10 mm (0.39 in.)

Input Specifications – 2005-IA8 and 2085-IM8

Attribute

2085-IA8

2085-IM8

Min

Max

Solid

0.34 mm

2

(22 AWG)

2.5 mm

2

(14 AWG)

Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max

Stranded

0.20 mm

2

2.5 mm

2

(14 AWG)