Derating curve for 2085-iq16, Derating curve for 2085-iq32t – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual

Page 54

Advertising
background image

46

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

Appendix A Specifications

Derating Curve for 2085-IQ16

Derating Curve for 2085-IQ32T

Status indicators

16 yellow indicators

32 yellow indicators

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V DC for 60 s

Enclosure type rating

Meets IP20

North American temp
code

T4

Operating voltage
range

10…30V DC, Class 2
21.6…26.4V AC, 50/60 Hz, Class 2
See

Derating Curve for 2085-IQ16

and

Derating Curve for 2085-IQ32T on

page 46

Off-state voltage, max

5V DC

Off-state current, max

1.5 mA

1.2 mA

On-state current, min

1.8 mA @ 10V DC

On-state current, nom

6.0 mA @ 24V DC

5.2 mA @ 24V DC

On-state current, max

8.0 mA @ 30V DC

7.0 mA @ 30V DC

Input impedance, max

3.9 k

Ω

4.6 k

Ω

IEC input compatibility

Type 3

Type 1

(1) Meets IEC Type 1 24V DC Input Specifications.

(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring

and Grounding Guidelines, publication

1770-4.1

.

(3) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules

(1)

Attribute

2085-IQ16

2085-IQ32T

30

26.4

30

°C

65

°C

Input voltage (V)

45302

Temp

30

26.4

32

24

30

°C

65

°C

18

24

Input voltage (V)

45301

Number

of inputs

Advertising