Output specifications – 2085-ov16 and 2085-ob16 – Rockwell Automation 2085 Micro800 Discrete and Analog Expansion I/O Modules User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

47

Specifications Appendix A

2085-OV16 Sink and 2085-OB16 Source DC Output Module

Attribute

2085-OV16

2085-OB16

Number of outputs

16 sinking

16 sourcing

Dimensions, HxWxD

44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)

Shipping weight,
approx.

220 g (7.76 oz)

Bus current draw,
max

200 mA @ 5V DC

Wire size

Wiring category

(1)

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring

and Grounding Guidelines, publication

1770-4.1.

2 – on signal ports

Terminal screw
torque, max

0.5…0.6 Nm
(4.4…5.3 lb-in.)

(2)

(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

Output circuit type

24V DC sink

24V DC source

Power dissipation,
total

5 W

Power supply

24V DC, Class 2

Status indicators

16 Yellow channel indicators

Isolation voltage

50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V AC for 60 s

Enclosure type
rating

Meets IP20

North American
temp code

T4

Output Specifications – 2085-OV16 and 2085-OB16

Attribute

2085-OV16

2085-OB16

Operating voltage range

10…30V DC

On-state voltage, min

10V DC

On-state voltage, nom

24V DC

On-state voltage, max

30V DC

On-state current, max

0.5 A @ 30V DC, per output
8 A, per module

On-state voltage drop, max

1.0V DC @ 0.5 A

Off-state leakage current, max

1 mA @ 30V DC

Min

Max

Solid

0.34 mm

2

(22 AWG)

2.5 mm

2

(14 AWG)

Copper wire rated @ 90 °C (194
°F), or greater, 1.2 mm
(3/64 in.) insulation max

Stranded

0.20 mm

2

2.5 mm

2

(14 AWG)

Advertising