Chapter 2 Discrete and Analog Expansion I/O Features

• Engineering Units – The module scales the analog input data to the actual

current or voltage values for the selected input range. The resolution of the
engineering units is 0.001V or 0.001 mA per count.

• Percent Range – The input data is presented as a percentage of the normal

operating range. For example, 0V…10V DC equals 0…100%. The amount
over and under the normal operating range (the full-scale range) is also
supported.

Valid Range of the Data Formats for 2085-IF4, 2085-IF8, and 2085-OF4

The valid range of each Data Format corresponds to the full range of each Type/
Range (or normal range). For example, the full range of 0…20 mA is 0…21 mA.

Valid Range of the 2085-IF4 and 2085-IF8 Data Formats

Data Format

Type/Range

0…20 mA

(4)

(4) The full range value of:

a. 0…20 mA is 0…21 mA
b. 4 to 20 mA is 3.2…21 mA
c. -10…10V is -10.5…10.5V
d. 0…10V is -0.5…10.5V

4…20 mA

(4)

-10…10V

(4)

0…10 V

(4)

Raw/Proportional Data

(1)

(1) See

Convert Analog Value to Data Format Value on page 9

.

-32768…32767

Engineering Units

(2)

(2) The resolution is 0.001V or 0.001 mA per count. For example, 9999 here means 9.999V or 9.999 mA

(or 9999 x 0.001).

0…21000

3200…21000

-10500…10500

-500…10500

Percent Range

(3)

(3) The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%). See

Convert

Analog Value to Data Format Value on page 9

0…10500

-500…10625

Not supported

-500…10500

Valid Range of the 2085-OF4 Data Formats

Data Format

Type/Range

0…20 mA

(4)

(4) The full range value of:

a. 0…20 mA is 0…21 mA
b. 4…20 mA is 3.2…21 mA
c. -10…10V is -10.5…10.5V
d. 0…10V is 0…10.5V

4…20 mA

(4)

-10…10V

(4)

0…10V

(4)

Raw/Proportional
Data

(1)

(1) See

Convert Analog Value to Data Format Value on page 9

.

-32768…32767

Engineering Units

(2)

(2) The resolution is 0.001V or 0.001 mA per count. For example, 9999 here means 9.999V or 9.999 mA (or 9999 x

0.001.

0…21000

3200…21000

-10500…10500

0…10500

Percent Range

(3)

(3) The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%). See

Convert

Analog Value to Data Format Value on page 9

.

0…10500

-500…10625

Not supported

0…10500