50

Rockwell Automation Publication 2080-UM003A-EN-E - March 2013

Appendix A Specifications

Analog Expansion I/O

Wiring category

(1)

2 – on signal ports

Wire type

Copper

Terminal screw
torque. max

0.5…0.6 Nm
(4.4…5.3 lb-in.)

(2)

Bus current draw, max

5V DC, 120 mA
24V DC, 50 mA

5V DC, 160 mA
24V DC, 100 mA

Load current, max

2 A

Power dissipation,
total

2.72 W

5.14 W

Relay contact,
(0.35 power factor)

Minimum load, per
point

10 mA per point

Off-state leakage, max 1.5 mA

Status indicators

8 yellow indicators

16 yellow indicators

Isolation voltage

240V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 3250V DC for 60 s

Pilot duty rating

C300, R150

Enclosure type rating

Meets IP20

North American temp
code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring

and Grounding Guidelines, publication

1770-4.1

.

(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.

2085-OW8 and 2085-OW16 Relay Output Module

Attribute

2085-OW8

2085-OW16

Max
Volts

Amperes

Amperes

Volt Amperes

Make

Break

Continuous Make

Break

120V AC

15 A

1.5 A

2.0 A

1800V A

180V A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

1.0 A

28V A

125V DC

0.22 A

2085-IF4, 2085-IF8, 2085-OF4 Analog Input and Output Modules

Attribute

2085-IF4

2085-OF4

2085-IF8

Number of I/O

4

8

Dimensions, HxWxD

28 x 90 x 87 mm
(1.1 x 3.54 x 3.42 in.)

44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)

Shipping weight,
approx.

140 g (4.93 oz)

220 g (7.76 oz)

Bus current draw,
max

5V DC, 100 mA
24V DC, 50 mA

5V DC, 160 mA
24V DC, 120 mA

5V DC, 110 mA
24V DC, 50 mA