Environment Specifications

Environment Specifications for Micro8

00 Expansion I/O Modules

Attribute

Value

Temperature, operating

IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40…185 °F)

Temperature, surrounding air, max. 65 °C (149 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g for DIN Rail Mounting
35 g for Panel Mounting

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Advertising