Installation and Alignment

Refer to Figures 3-21 or 3-23 for 2-channel EDM hookup.

Connect the monitor contacts as shown between +24V dc and

EDM1 (pin 3) and between +24V dc and EDM2 (pin 2). Set the

configuration DIP switch to E2, per Section 4.2.
NOTE: For EZ-SCREEN receivers with a date code prior to

0834, the monitoring contacts must always close within

200 milliseconds of the corresponding OSSD state

change (turning OFF) or a lockout will occur.

No Monitoring: Use this configuration initially, in order to

perform the initial checkout; see Section 3.6. If the application

does not require the EDM function, it is the user’s responsibility

to ensure that this configuration does not create a hazardous

situation.
Refer to Figure 3-22 for “no monitoring” hookup. To configure

the EZ-SCREEN for no monitoring, connect or jumper EDM1

(pin 3) to EDM2 (pin 2) using the supplied wire-nut. Set the

configuration DIP switch to E2, per Section 4.2.
An alternate method to configure no monitoring is to set the

configuration DIP switch to E1 (1-channel monitoring), per

Section 4.2, and connect EDM1 (pin 3) to +24V dc. This method

allows the ability to use the auxiliary output (see Section 3.5.5)

in applications that do not require the EDM function.

3.5.4 Optional Remote Test Input

A pair of connections is provided on 5-pin emitters (Test1 and

Test2) for the connection of an external remote test switch

(typically a normally open contact held closed). Opening this

switch “turns OFF” the emitter, simulating an interruption of the

light beams; all OSSD outputs will turn OFF. See Sections 2.7.2,

3.3.1, and Figure 3-20.

3.5.5 Auxiliary (Aux) Output

On EZ-SCREEN receivers with date code 0834 or newer,

an auxiliary status output is available that provides a PNP

current-sourcing output (75 mA max.) that mirrors the state of

the OSSDs. The output is on pin 2 (orange/black wire) when

the EDM configuration DIP switch is set to E1 (1-channel

monitoring), per Section 4.2. See the 1-channel EDM circuit on

Figure 3-23 for hookup information.
To use the auxiliary output in an application configured for no

monitoring, set the configuration DIP switch to E1 (1-channel

monitoring) per Section 4.2., and connect EDM1 (pin 3) to

+24V dc (see Section 3.5.3).
There are no compatibility issues retrofitting receivers with

aux output into earlier installations, if precautions are taken to

prevent EDM2 (pin 2, orange/black wire) from shorting to ground

or another source of energy.

Safety Output

250 ms

Max.

250 ms

Max.

250 ms

Max.

250 ms

Max.

Don’t Care

Closed

Open

Closed

Open

EDM 1

EDM 2

Figure 3-17. Two-channel EDM, timing between channels

Figure 3-18. Two-channel EDM status, with respect to safety

output

Refer to Figure 3-23 for 1-channel EDM hookup. Connect the

monitor contacts between +24V dc and EDM1 (pin 3). Leave

EDM2 (pin 2) open (no connection). Set the configuration DIP

switch to E1, per Section 4.2.
NOTE: For EZ-SCREEN receivers with a date code prior to

0834, the monitoring contacts must open within 200

milliseconds of the OSSD outputs turning ON (a clear

condition) and must close within 200 milliseconds of the

OSSD outputs turning OFF (a blocked condition) or a

lockout will occur.

Two-Channel Monitoring: This is an independent connection

of closed monitor contacts that are forced-guided (mechanically

linked) from each device controlled by the EZ-SCREEN. The

monitor contacts must be closed before the EZ-SCREEN can be

reset and the OSSDs can turn ON. Regardless of the state of

the OSSDs, the monitor contacts may change state (either both

open, or both closed). If the monitor contacts remain in opposite

states for more than 250 milliseconds, a lockout will occur.

Safety Output

Closed

Open

Closed

Open

OFF

ON

EDM 1

EDM 2

Must Match EDM 1

Must Match EDM 1

Must Match EDM 2

Must Match EDM 2

Must Match EDM 1

Must Match EDM 1

Must Match EDM 2

Must Match EDM 2