Overview

60

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com

Tel: 763.544.3164

EZ-SCREEN

Instruction Manual

Cascadeable EZ-SCREEN

Figure 7-6. Calculating response times for a three-light screen cascade – both Individual and Overall methods

Machine

Control

Machine

Control

Machine

Control

Emitters

Receivers

Emitters

Receivers

Emitters

Receivers

When contacts (e.g., an E-stop button) are connected to a

cascaded receiver (per Section 7.8), CSSI response time is

40 ms plus the 2 ms adder similar to the defined area Tr.

Tr

(CSSI)

= 40 ms + [(N-1) x 2 ms]

Cascade Configuration vs. Response Time

When light screens of different lengths or different resolutions

(and therefore different response times) are used in one circuit,

their positions in the cascade may become a consideration.
For example, consider the light screen circuits depicted in Figure

7-6. Each example contains three safety light screens, one 1200

mm (with a response time of 40 ms), and two 300 mm light

screens (15 ms response each). Depending on their placement

in the cascade, the individual response time for the same three

light screens can vary from 40 to 44 ms.

EZ-SCREEN

Position #3
40 + 2 + 2 = 44
Individual Response

Time: 44 ms

Emitters

Receivers

EZ-SCREEN

Position #3
15 + 2 + 2 = 19
Individual Response

Time: 19 ms

Emitters

Receivers

EZ-SCREEN

Position #3
15 + 2 + 2 = 19
Individual Response

Time: 19 ms

Emitters

Receivers

EZ-SCREEN

Position #2
15 + 2 = 17
Individual Response

Time: 17 ms

EZ-SCREEN

Position #2
40 + 2 = 42
Individual Response

Time: 42 ms

EZ-SCREEN

Position #2
15 + 2 = 17
Individual Response

Time: 17 ms

EZ-SCREEN

Position #1
Individual Response

Time: 15 ms

EZ-SCREEN

Position #1
Individual Response

Time: 15 ms

EZ-SCREEN

Position #1
Individual Response

Time: 40 ms

Machine

Control

Machine

Control

Machine

Control

System Overall Response Time for all systems shown here is 40 + [(3 – 1) × 2 ms] = 44 ms