AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS

558D036 (3 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

900

0.67

0.21

253

0.68

0.23

277

0.69

0.26

307

0.69

0.31

363

1000

0.60

0.23

270

0.61

0.25

292

0.61

0.27

321

0.63

0.32

374

1100

0.55

0.24

287

0.56

0.26

307

0.57

0.28

335

0.58

0.33

385

1200

0.51

0.26

304

0.51

0.27

323

0.52

0.29

349

0.53

0.34

397

1300

0.45

0.27

321

0.46

0.29

338

0.46

0.31

364

0.47

0.34

408

1400

0.38

0.29

338

0.41

0.30

354

0.43

0.32

378

1500

0.34

0.30

355

0.36

0.31

369

0.38

0.33

392

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using your

fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D036 (3 TON)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

581

0.12

119

673

0.18

179

736

0.22

219

805

0.25

249

865

0.29

288

911

0.34

338

1000

644

0.19

189

709

0.22

219

782

0.28

279

835

0.30

298

900

0.35

348

937

0.38

378

1100

687

0.22

219

746

0.26

259

806

0.30

298

867

0.35

348

929

0.40

398

964

0.40

398

1200

733

0.26

259

785

0.32

318

843

0.35

348

903

0.41

408

960

0.47

467

994

0.50

497

1300

754

0.29

288

826

0.38

378

891

0.43

428

942

0.48

477

991

0.53

527

1047

0.60

597

1400

810

0.35

348

868

0.45

448

937

0.51

507

984

0.57

567

1032

0.62

617

1067

0.67

666

1500

841

0.42

418

911

0.53

527

985

0.61

607

1029

0.66

656

1073

0.72

716

1109

0.77

766

558D036 (3 TON) (cont)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.7

0.8

0.9

1.0

1.1

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

900

957

0.39

388

988

0.43

428

1039

0.45

448

1061

0.47

487

1083

0.53

527

1105

0.57

567

1000

992

0.44

438

1039

0.49

487

1061

0.51

507

1086

0.55

547

1111

0.59

587

1136

0.63

627

1100

1013

0.49

487

1068

0.55

547

1090

0.58

577

1109

0.61

607

1127

0.64

637

1145

0.67

666

1200

1045

0.56

557

1090

0.64

637

1109

0.64

647

1156

0.68

676

1203

0.71

706

1250

0.74

736

1300

1075

0.64

637

1122

0.70

696

1152

0.72

716

1190

0.76

756

1228

0.80

796

1266

0.84

836

1400

1110

0.73

726

1160

0.84

766

1181

0.81

806

1237

0.85

845

1293

0.89

885

1349

0.93

925

1500

1150

0.82

816

1190

1.00

855

1225

0.90

895

1271

0.95

945

1317

1.00

995

1363

1.05

1044

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 1000 and maximum continuous bhp

is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 760 to 1000 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.