AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)

558D060 (5 TON)

Airflow

(Cfm)

Standard Direct-Drive Motor

Low Speed

Medium Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

1500

0.88

0.67

750

1.20

0.71

791

1.19

0.70

782

1.36

0.76

845

1.38

0.79

875

1.44

0.85

949

1600

0.68

0.70

780

1.04

0.74

824

1.04

0.74

821

1.22

0.79

883

1.25

0.82

913

1.33

0.89

988

1700

0.51

0.73

810

0.89

0.77

857

0.89

0.77

861

1.09

0.83

921

1.13

0.85

950

1.22

0.92

1027

1800

0.35

0.75

839

0.73

0.80

891

0.74

0.81

900

0.96

0.86

959

1.00

0.89

988

1.11

0.96

1066

1900

0.26

0.78

873

0.58

0.83

924

0.59

0.84

940

0.86

0.90

997

0.88

0.92

1025

1.00

0.99

1105

2000

0.18

0.81

905

0.42

0.86

957

0.44

0.88

979

0.73

0.93

1035

0.78

0.95

1063

0.92

1.03

1144

2100

0.08

0.84

940

0.27

0.89

990

0.29

0.91

1018

0.59

0.96

1073

0.63

0.99

1101

0.81

1.06

1183

2200

0.19

0.92

1023

0.19

0.93

1035

0.46

1.00

1111

0.49

1.02

1138

0.69

1.10

1222

2300

0.11

0.95

1056

0.11

0.97

1076

0.34

1.03

1149

0.41

1.06

1176

0.59

1.13

1261

2400

0.03

0.98

1096

0.04

1.00

1113

0.19

1.07

1187

0.22

1.09

1213

0.43

1.17

1300

2500

0.09

1.10

1225

0.12

1.12

1251

0.34

1.20

1340

LEGEND

Bhp

Brake Horsepower Input to Fan

ESP

External Static Pressure (in. wg)

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

2. Extensive motor and electrical testing on these units ensures that the

full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

3. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

4. Minimum allowable cfm is 300 cfm/ton.

558D060 (5 TON)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.4

0.6

0.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

730

0.34

347

789

0.40

409

896

0.53

542

990

0.67

685

1072

0.83

848

1600

770

0.40

409

826

0.46

470

931

0.61

623

1020

0.75

766

1101

0.91

930

1700

811

0.47

480

865

0.54

552

966

0.69

705

1051

0.84

858

1133

1.01

1032

1800

852

0.55

562

905

0.62

634

1002

0.78

797

1084

0.93

950

1163

1.10

1124

1900

894

0.54

552

945

0.72

736

1037

0.88

899

1119

1.04

1063

1194

1.21

1237

2000

936

0.74

756

984

0.82

838

1072

0.98

1001

1154

1.16

1185

1226

1.33

1359

2100

978

0.85

869

1024

0.93

950

1108

1.10

1124

1192

1.29

1318

1259

1.47

1502

2200

1021

0.97

991

1064

1.05

1073

1145

1.22

1247

1225

1.43

1461

1294

1.62

1656

2300

1064

1.10

1124

1104

1.18

1206

1183

1.36

1390

1260

1.57

1604

1330

1.78

1819

2400

1107

1.24

1267

1145

1.32

1349

1222

1.45

1482

1296

1.73

1768

1365

1.94

1983

2500

1150

1.39

1420

1186

1.48

1512

1262

1.68

1717

1331

1.80

1921

1400

2.12

2166

558D060 (5 TON) (cont)

Airflow

(Cfm)

Alternate Belt-Drive Motor

External Static Pressure (in. wg)

1.0

1.2

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1153

1.00

1022

1221

1.17

1196

1256

1.30

1328

1280

1.32

1349

1320

1.22

1400

1600

1178

1.09

1114

1252

1.27

1298

1311

1.45

1482

1340

1.58

1615

1380

1.61

1645

1700

1205

1.18

1206

1278

1.37

1400

1345

1.57

1604

1397

1.76

1799

1424

1.89

1931

1800

1235

1.29

1318

1303

1.48

1512

1371

1.69

1727

1433

1.90

1942

1480

2.09

2136

1900

1266

1.40

1431

1330

1.59

1625

1396

1.80

1850

1460

2.03

2074

1517

2.25

2299

2000

1297

1.53

1564

1362

1.73

1768

1422

1.94

1983

1485

2.16

2207

1544

2.40

2453

2100

1327

1.66

1696

1393

1.80

1911

1452

2.08

2126

1510

2.31

2361

1569

2.55

2606

2200

1359

1.80

1850

1423

2.02

2064

1483

2.24

2289

1538

2.46

2514

1595

2.71

2769

2300

1392

1.97

2013

1454

2.18

2228

1515

2.41

2463

1569

2.64

2698

1622

2.88

2943

2400

1426

2.15

2197

1485

2.36

2412

1544

2.59

2647

1601

2.84

2902

1652

3.07

3137

2500

1461

2.34

2391

1518

2.55

2606

1575

2.78

2841

1631

3.03

3096

1684

3.28

3352

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 1921 and maximum continuous bhp

is 1.80. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 900 to 1300 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.