AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS (cont)

558D072 (6 TON)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

0.1

0.2

0.4

0.6

0.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

852

0.55

562

905

0.62

615

1002

0.78

739

1084

0.93

859

1163

1.10

998

1900

894

0.64

630

945

0.72

692

1037

0.88

818

1119

1.04

948

1194

1.21

1089

2000

936

0.74

708

984

0.82

771

1072

0.98

899

1154

1.16

1047

1226

1.33

1190

2100

978

0.85

795

1024

0.93

859

1108

1.10

998

1190

1.29

1156

1259

1.47

1310

2200

1021

0.97

891

1064

1.05

956

1145

1.22

1097

1225

1.43

1275

1294

1.62

1439

2300

1064

1.10

998

1104

1.18

1064

1183

1.36

1216

1260

1.57

1396

1330

1.78

1578

2400

1107

1.24

1114

1145

1.32

1182

1222

1.52

1353

1296

1.73

1534

1365

1.94

1718

2500

1150

1.39

1241

1186

1.48

1318

1262

1.68

1491

1331

1.89

1674

1400

2.12

1875

2600

1193

1.56

1387

1228

1.65

1465

1301

1.86

1648

1367

2.07

1831

1435

2.31

2041

2700

1237

1.74

1543

1269

1.83

1621

1341

2.05

1814

1404

2.26

1997

1471

2.51

2214

2800

1280

1.94

1718

1311

2.03

1796

1381

2.25

1989

1442

2.47

2180

1506

2.72

2394

2900

1324

2.15

1901

1354

2.24

1980

1420

2.47

2180

1481

2.69

2369

1542

2.94

2579

3000

1368

2.37

2093

1396

2.46

2171

1460

2.69

2369

1521

2.93

2571

558D072 (6 TON) (cont)

Airflow

(Cfm)

Standard Belt-Drive Motor

External Static Pressure (in. wg)

1.0

1.2

1.4

1.6

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1800

1235

1.29

1156

1303

1.48

1318

1371

1.69

1499

1433

1.90

1638

1900

1266

1.40

1250

1330

1.59

1413

1396

1.81

1604

1460

2.03

1796

2000

1297

1.53

1361

1362

1.73

1534

1422

1.94

1718

1485

2.16

1910

2100

1327

1.66

1473

1393

1.87

1656

1452

2.08

1840

1510

2.31

2041

2200

1359

1.81

1604

1423

2.02

1779

1483

2.24

1980

1538

2.46

2171

2300

1392

1.97

1744

1454

2.18

1927

1515

2.41

2128

1569

2.64

2326

2400

1426

2.15

1901

1485

2.36

2084

1544

2.59

2283

1601

2.84

2459

2500

1461

2.34

2067

1518

2.55

2249

1575

2.78

2445

2600

1497

2.54

2240

1552

2.76

2428

2700

1532

2.75

2420

2800

2900

3000

LEGEND

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)

2.

indicates field-supplied motor and drive are required.

3.

indicates maximum usable bhp/watts.

4. Maximum usable watts input is 2120 and maximum continuous bhp

is 2.40. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using

your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.

5. Values include losses for filters, unit casing, and wet coils. See

page 47 for accessory/FIOP static pressure information.

6. Use of a field-supplied motor may affect wire sizing. Contact your lo-

cal representative for details.

7. Motor drive range: 1070 to 1460 rpm. All other rpms require field-

supplied drive.

8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.